ELECTRICAL METALLIC TUBING
Metric Data  |  Home   |  Sales Staff   |  Sales Agents  |  Distributor  List
Rigid Steel Conduit   |    Intermediate Steel Conduit   |  Electrical Conduit

Hot Zinc Coated
Special clear secondary coating applied after galvanizing provides added corrosion protection
E
lectrical Metallic Tubing
WESTERN E.M.T provides uniformity of weight, wall thickness, O.D. and I.D. concentricity, ductility and maximum strength

Western E.M.T. is made from strip steel, high frequency welded. A continuous hot galvanized process is employed to coat exterior surfaces evenly and smoothly; a special transparent secondary coating provides further protection against corrosion. Manufactured in accordance with Under-writers Laboratories UL-797, American National Standards Specifications C-80.3, Federal Specifications WW-C-563A. Approved by the 1987 National Electric Code article 348, for open, concealed and concrete slab installations.

Quality Controlled each step of the way - Regular tests for weld strength, Malleability, plating thickness and uniform smoothness of interior coating provides you with conduit of highest quality.... Western E.M.T.

Easy to bend- Perfect bends and offsets can be made quickly with lightweight easy to handle Western EMT.

Easy, trouble free wire pulling- A special baked-on coating on inside of surface of Western E.M.T. reduces friction and provides extra ease in wire installation.

 

 

No chipping, cracking, peeling-Outside surfaces are galvanized with zinc coating for superior corrosion resistance and long-lasting, dependable service. Special protective coating is then applied.

  • Compatible with all types of building materials.
  • Provides a lifetime of safe electrical installations.
  • Low in cost - strong, durable.

ARCHITECTS HOT ZINC COATED CONDUIT SPECIFICATIONS

To specify Western Hot Zinc Coated E.M.T. include the following: Electrical Conductors shall be enclosed in Western Hot Zinc Coated E.M.T. in accordance with the National Electrical Code. Electric Metallic Tubing shall be steel, electrically welded, hot zinc galvanized and produced to ANSI Specifications C-80.3 and Federal Specification WW-C-563A latest revisions, and shall carry the Underwriters Laboratories label, as manufactured by Western Tube and Conduit Corporation.

 

WEIGHTS DIMENSIONS AND STANDARD PACKAGING
SIZE APPROX. WT
PER 1000 FT.
DIAMETER
INSIDE
DIAMETER
OUTSIDE
WALL
THICKNESS
FEET PER
UNIT BUNDLE
FEET PER
STANDARD LIFT
WEIGHT PER
STANDARD LIFT
1/2" 295 lbs. 0.622 0.706 0.042 100 7000 2090
3/4" 445 lbs. 0.824 0.922 0.049 100 5000 2288
1" 650 lbs. 1.049 1.163 0.057 100 3000 2020
1 1/4" 960 lbs. 1.380 1.510 0.065 50 2000 2010
1 1/2" 1110 lbs. 1.610 1.740 0.065 50 1500 1740
2" 1410 lbs. 2.067 2.197 0.065 30 1200 1780
2 1/2" 2300 lbs. 2.731 2.875 0.072 1 610 1320
3" 2700 lbs. 3.356 3.500 0.072 1 510 1340
3 1/2" 3260 lbs. 3.834 4.000 0.083 1 370 1290
4" 4000 lbs. 4.334 4.500 0.083 1 300 1180
               

AMPLE STOCK MAINTAINED AT ALL TIMES FOR PROMPT MILL SHIPMENT.